Single-conductor cables used in portable earthing and bridging devices.
Conductor:
Copper, multi-wire, flexible class 6 (acc. to EN 60228)
Insulation:
PVC, type TM 6 (acc. to EN 50363-4-2)
Cables can be used in overhead and indoor conditions within temperatures from -25°C to +55°C.
Standard: EN 61138
Cables conform to the requirements of REACH Regulation and RoHS Directive.
Nominal cross-section | Single wire diameter | Resistance at 20°C | Wall insulation thickness | Outer diameter of cable | |
---|---|---|---|---|---|
(max.) | (max.) | (nom.) | (min.) | (max.) | |
mm2 | mm | mΩ/m | mm | mm | |
16 | 0,2 | 1,210 | 1,2 | 7,1 | 8,6 |
25 | 0,2 | 0,780 | 1,2 | 8,4 | 10,2 |
35 | 0,2 | 0,554 | 1,2 | 9,7 | 11,7 |
50 | 0,2 | 0,386 | 1,5 | 11,7 | 14,2 |
70 | 0,2 | 0,272 | 1,8 | 13,4 | 16,2 |
95 | 0,2 | 0,206 | 1,8 | 15,5 | 18,7 |
120 | 0,2 | 0,161 | 1,8 | 17,1 | 20,6 |